Thermal Overload Relay JLR2-D13
Karakteristik gerak: Tilu-fase Balance Motion Time
No | Waktu setelan ayeuna (A) | waktos gerak | Kaayaan ngamimitian | Suhu lingkungan | ||
1 | 1.05 | > 2 jam | kaayaan tiis | 20±5°C
| ||
2 | 1.2 | <2 jam | kaayaan panas | |||
3 | 1.5 | <4 mnt | (Sanggeus tes No.l) | |||
4 | 7.2 | 10A | 2s | <63A | kaayaan tiis | |
10 | 4s | > 63A |
Fase-leungitna Ciri Gerak
No | Waktu setelan ayeuna (A) | waktos gerak | Kaayaan ngamimitian | Suhu lingkungan | |
Sakur dua fase | Fase séjén | ||||
1 | 1.0 | 0.9 | > 2 jam | kaayaan tiis | 20±5°C |
2 | 1.15 | 0 | <2 jam | kaayaan panas (Sanggeus tes No.l) |
Spésifikasi
Tipe | Jumlah | Rentang setelan (A) | Pikeun contactor |
JLR2-D13
| 1301 | 0.1~0.16 | JLC1-09~32 |
1302 | 0.16~0.25 | JLC1-09~32 | |
1303 | 0.25~0.4 | JLC1-09~32 | |
1304 | 0.4~0.63 | JLC1-09~32 | |
1305 | 0.63~1 | JLC1-09~32 | |
1306 | 1~1.6 | JLC1-09~32 | |
1307 | 1.6~2.5 | JLC1-09~32 | |
1308 | 2.5~4 | JLC1-09~32 | |
1310 | 4~6 | JLC1-09~32 | |
1312 | 5.5~8 | JLC1-09~32 | |
1314 | 7~10 | JLC1-09~32 | |
1316 | 9~13 | JLC1-09~32 | |
1321 | 12~18 | JLC1-09~32 | |
1322 | 17~25 | JLC1-32 | |
JLR2-D23
| 2353 | 23~32 | CJX2-09~32 |
2355 | 30~40 | JLC1-09~32 | |
JLR2-D33
| 3322 | 17~25 | JLC1-09~32 |
3353 | 23~32 | JLC1-09~32 | |
3355 | 30~40 | JLC1-09~32 | |
3357 | 37~50 | JLC1-09~32 | |
3359 | 48~65 | JLC1-09~32 | |
3361 | 55~70 | JLC1-09~32 | |
3363 | 63-80 | JLC1-09~32 | |
3365 | 80~93 | JLC1-95 | |
JLR2-D43
| 4365 | 80~104 | JLC1-95 |
4367 | 95~120 | JLC1-95~115 | |
4369 | 110~140 | JLC1-115 |
Outline Jeung Mounting Dimensi
Asesoris
Skenario aplikasi:
Biasana dipasang dina kotak distribusi di lantai, pusat komputer, ruang telekomunikasi, ruang kontrol lift, kamar TV kabel, kamar kontrol wangunan, puseur seuneu, wewengkon kontrol otomatis industri, kamar operasi rumah sakit, kamar monitoring sarta kotak distribution parabot jeung alat médis éléktronik. .